Infractions found

Inspection history

Jun 3, 2026 · Compliance Inspection
Infractions found
  • Non-critical Sufficient supply and storage of chemicals and testing devices
    Inspector's note: Not in Compliance: Ensure testing devices are adequate and sufficient to operate the pool
Aug 13, 2025 · Compliance Inspection
Infractions found
  • Non-critical Other records signed and completed
    Inspector's note: Not in Compliance: Ensure cyanuric acid levels are monitored and recorded weekly, Ensure water outlet cover inspections are recorded at least once every 30 operating days along with time of day the test was completed and by whom
  • Critical Safety equipment available and in good repair
    Inspector's note: Not in Compliance: Ensure all safety equipment is maintained in good repair, Provide all safety equipment in places conveniently located for emergency use
  • Non-critical Sufficient supply and storage of chemicals and testing devices
    Inspector's note: Not in Compliance: Ensure supply of chemicals are sufficient to operate the pool
  • Non-critical Daily records completed, signed and maintained
    Inspector's note: Not in Compliance: Record reading of the make-up water meter daily, Record time of day for testing of emergency telephone daily, Emergency telephone must be tested to confirm that is in operating condition before the pool or spa is opened for use each day
  • Critical Outlet covers are secure and inspected at least once every 30 operating days
    Inspector's note: Not in Compliance: Ensure water outlet covers are inspected at least once every 30 operating days
May 16, 2025 · Compliance Inspection
Infractions found
  • Critical Outlet covers are secure and inspected at least once every 30 operating days
    Inspector's note: Not in Compliance: Ensure water outlet covers are inspected at least once every 30 operating days
  • Non-critical Other records signed and completed
    Inspector's note: Not in Compliance: Ensure cyanuric acid levels are monitored and recorded weekly, Ensure water outlet cover inspections are recorded at least once every 30 operating days along with time of day the test was completed and by whom, Ensure ground fault detector is tested and recorded monthly or according to the manufacturer–s instructions, whichever is more frequent
  • Critical All components of the filtration, recirculation, and chemical feed systems are in continuous operation and maintained in proper working order
    Inspector's note: Not in Compliance: Ensure automatic sensing device displays sanitizer levels and pH
  • Non-critical Sufficient supply and storage of chemicals and testing devices
    Inspector's note: Not in Compliance
  • Non-critical Daily records completed, signed and maintained
    Inspector's note: Not in Compliance: Complete and sign records daily, Automatic sensing device- record Chlorine (free and total) – hour before opening & every 4 hours while pool is open, Automatic sensing device- record pH – hour before opening & every 4 hours while pool is open, Automatic sensing device- record alkalinity – hour before opening & every 4 hours while open, Automatic sensing device- record clarity of pool – hour before opening & every 4 hours while open, Record any emergencies, rescues, or breakdown of equipment that have occurred, Record reading of the make-up water meter daily, Record time of day for testing of emergency telephone daily, Record total number of bathers admitted to facility each day, Record type and amount of chemicals added manually daily, Ensure all records are available for viewing and are kept for a period of one year, Emergency telephone must be tested to confirm that is in operating condition before the pool or spa is opened for use each day
  • Non-critical "Pool Rules" notices displayed with complete information
    Inspector's note: Corrected During Inspection: Ensure the maximum number of bathers is indicated on the "Pool Rules" notices
Jul 29, 2024 · Compliance Inspection
Infractions found
  • Non-critical Daily records completed, signed and maintained
    Inspector's note: Not in Compliance: Complete and sign records daily
  • Non-critical Manual chemical testing in compliance
    Inspector's note: Not in Compliance: Automatic Sensing Device - Ensure pH, alkalinity, Free Available Chlorine, total chlorine or bromine residuals and water clarity are tested manually one half hour before bathers are admitted, and checked at least every 4 hours during the operating day